CISA flags six Dorsett InfoScan flaws in water systems
Six CVEs covering stolen credentials, unaudited TLS, and hard-coded crypto keys close with a single update to v1.46.
TL;DR
CISA advisory ICSA-26-321-01 details six vulnerabilities in Dorsett Controls InfoScan v1.45.0 and earlier, deployed in water and wastewater systems worldwide. The flaws can let an attacker recover stored credentials, access application data without authorization, and intercept or manipulate network communications. Dorsett Controls says to update to v1.46 or higher through System Maintenance, or from the customer portal for offline installs.
CISA published advisory ICSA-26-321-01 on November 17, listing six CVEs in Dorsett Controls InfoScan, SCADA software used in water and wastewater systems worldwide. The affected range is InfoScan v1.45.0 and earlier, and the vendor fix is a single update to v1.46 or higher.
The advisory groups the flaws under five weakness types: improper certificate validation, exposure of sensitive system information, use of a hard-coded cryptographic key, missing authentication for a critical function, and error messages that disclose sensitive information. The details that CISA does supply are worth reading closely. CVE-2026-117659 concerns the Electron desktop client, which accepts TLS certificates without checking them and ships with nodeIntegration enabled, contextIsolation disabled, and webSecurity disabled. CVE-2026-120157 refers to installer configuration files that expose hostnames for customer installations and internal development, testing, and database infrastructure. CVE-2026-120255 uses hard-coded keys and initialization vectors to encrypt the MongoDB password before it lands in the Windows registry, so anyone with the registry value and the application code can recover the database password. CVE-2026-120260 doesn't enforce authentication on an endpoint for sales-automation templates, which a local attacker can query without a session.
The vendor gives one remediation path for all affected versions. Administrators log into InfoScan, open System Maintenance, select Check for Updates, and click Install Now. Offline customers download the update from the Dorsett Controls Customer Portal instead.
Published ·Deep Fathom